3 Phase Balancing is often calculated with the objective of distributing loads on all the three phases of a 3-phase electrical system. This often calls for an optimization of the system performance with minimization of loss; that is, the losses generated and at the same time avoid the damage of equipment. For businesses such as cement equipment suppliers, where heavy machinery requires a stable power supply, 3-phase balancing is crucial. Here is the step-by-step procedure on how to calculate three-phase balancing:
Balancing of Three-Phase Calculations Steps
1. Calculate the total load in each phase viz. A, B and C. It could be measured either in kilo-watts (kW) or kilo-volt-amperes (kVA).
PA=Power on Phase A PB=Power on Phase B PC=Power on Phase C
2. Total Load; Find the total load across the three phase:
Load Imbalance Computation Determine load imbalance for each phase by finding the variation between the load of each phase and the average load:
3.Average Load; Find the average load per phase:
4.Load imbalance calculation; Find the load imbalance of each phase. This is done by subtracting the average load in the phase from the load in each phase:
5.The screen should look like this:
Ideally, the imbalances should be close to zero. A balanced system means that each phase has approximately the same load. If the imbalances are significant, you may need to redistribute loads in order to achieve balance.
6. Calculate Percent Imbalance:
You can express the degree of imbalance quantitatively by computing the percentage imbalance:
Example Calculation
Let’s say the loads in each phase are as follows:
· PA=30kW · PB=45 kW · PC=25 kW
Step 1: calculate the total load:
Ptotal=30+45+25=100kW
Step 2: calculate average load
Pavg=100/3≈33.33kW
Step 3: calculate the load imbalance
Step 4: Calculate percent imbalance for each phase:
Conclusion
Ideally, a well-balanced three-phase system should have a percent imbalance of less than 5-10% to function at its best. Higher imbalances may need to have a redistribution of loads among the phases or the installation of additional balancing equipment such as phase balancers or transformers.